Ampacity Chart - Selected NEC Table 310.16 Values, Copper and Aluminum

The common conductor sizes at 60, 75 and 90 C, in both metals, on one page: the ten-second first answer every wire sizing starts from, with the tools that finish the job linked where the chart hands over to them.

Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.

Contents

An ampacity chart answers one question: how much current a conductor of a given size and material may carry continuously before its insulation runs too hot. This page carries the sizes working electricians and designers actually reach for, in both metals and all three temperature columns, so the number can be read in seconds and then carried into the sizing tools that finish the job.

Source and scope: values are selected from NEC Table 310.16 (Allowable Ampacities of Insulated Conductors), as carried in this site's own calculation data. They cover the common sizes, 14 AWG through 4/0 plus 250, 350 and 500 kcmil, at the 60, 75 and 90 C columns. This is a selection for planning, not the full table: the NEC table also lists the sizes between these, additional temperature and insulation rows, and the notes and conditions that govern their use. For a permitted installation, the table in the adopted edition of the NEC is the document of record.

Copper ampacity chart, selected sizes

Copper size60 C75 C90 C
14 AWG202025
12 AWG252530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
350 kcmil260310350
500 kcmil320380430

Two overlays sit on top of these numbers for small branch circuits: 240.4(D) caps the overcurrent device at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper regardless of the column, which is why the familiar 15, 20 and 30 A circuits pair with those sizes even though the 75 and 90 C columns read higher.

Aluminum ampacity chart, selected sizes

Aluminum size60 C75 C90 C
12 AWG152025
10 AWG253035
8 AWG304045
6 AWG405060
4 AWG556575
3 AWG657585
2 AWG7590100
1 AWG85100115
1/0 AWG100120135
2/0 AWG115135150
3/0 AWG130155175
4/0 AWG150180205
250 kcmil170205230
350 kcmil210250280
500 kcmil260310350

Aluminum runs roughly two sizes behind copper for the same ampacity, which is the trade behind its feeder economics: 2/0 aluminum carries about what 1/0 copper does. The 240.4(D) caps apply here too, at 15 A for 12 AWG and 25 A for 10 AWG aluminum.

Which temperature column applies to your circuit

The column is chosen by the terminations, not by the wire's insulation print. Under 110.14(C), circuits of 100 A and below default to the 60 C column unless the equipment is listed and marked for 75 C, and circuits above 100 A default to 75 C. Most modern breakers and lugs carry a 75 C rating, which is why the 75 C column is the working column on most pages of this site. The 90 C column is real but narrow in use: it is the starting point for derating calculations, where a 90 C conductor in a hot or crowded raceway may be adjusted downward, as long as the final figure does not exceed what the termination column allows.

What happens after the chart: derating and voltage drop

The chart value is the beginning of a conductor decision, not the end of one. Ambient temperature and the number of current-carrying conductors in the raceway adjust it down; the 240.4(D) caps and the termination column bound it; and on any run of real length, voltage drop can demand a larger conductor than ampacity ever asked for. The wire size calculator runs the whole chain in one pass, starting from these same table values, applying temperature and raceway adjustment, and naming the check that governed. The voltage drop calculator isolates the length question on its own, and the conduit fill calculator checks that the chosen conductors physically fit the raceway. Between them, every number on this page can be carried to a finished circuit without leaving the site.

Worked reading: a 100 A feeder

A 100 A feeder on copper, equipment marked 75 C: read the copper chart at the 75 C column and the first size reaching 100 A is 3 AWG, at exactly 100. On aluminum the same reading lands on 1 AWG, also 100 at 75 C. Neither answer is final until derating and voltage drop have had their say, which is the worked example the wire size calculator opens with. The chart's job in that chain is what it has always been: a ten-second first answer that the rest of the method then tests.

Questions

What is the ampacity of 12 AWG copper?

25 A at 60 C, 25 A at 75 C and 30 A at 90 C in Table 310.16. In practice the overcurrent device on a 12 AWG copper branch circuit is capped at 20 A by 240.4(D), so the chart figure and the circuit rating are different numbers, both correct in their own frame.

What size wire do I need for 100 amps?

On the chart alone, 3 AWG copper or 1 AWG aluminum at the 75 C column, each exactly 100 A. Treat that as the floor: derating for temperature or conductor count, and voltage drop over the run, can each push the answer larger, and the wire size calculator applies both.

Why are there three temperature columns?

Because ampacity is a thermal limit and insulation systems tolerate different temperatures. A conductor insulated for 90 C can carry more current before reaching its limit than the same conductor in a 60 C system. The column you may use is set by the lowest-rated element in the chain, usually the termination, per 110.14(C).

Can I use the 90 C column if my wire is rated 90 C?

For the final ampacity, only if the terminations are also rated 90 C, which is uncommon in building work. The standard use of the 90 C column is as the starting value for derating: adjust down from 90 C, then cap the result at the 75 C or 60 C termination value.

Is this the complete NEC Table 310.16?

No, deliberately. This page carries selected common sizes from the table for planning and cross-checking, in the same data the site's calculators use. The complete table, with every size, insulation type and condition of use, is published in the NEC itself, and permitted work is specified from that document, not from a chart page.

Planning-level reference. Conductor decisions on permitted work follow the adopted NEC edition, the equipment listing and the authority having jurisdiction. Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.