How Far Can You Run 12 Gauge Wire - Voltage Drop Limits by Load
On 12 AWG copper, distance is a current question before it is a length question: at 20 A the customary 3 percent voltage drop budget is spent in about 46 feet, while at 10 A the same wire runs about 93 feet. This guide tabulates the limits by load and shows when stepping up to 10 AWG is the better answer.
Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.
The distance table
Figures use the NEC Chapter 9 resistance basis this site's calculators use, 1.93 ohms per 1,000 feet for 12 AWG copper, with drop figured on the out-and-back path of a single-phase circuit. Distances are one-way, panel to load.
| Load on the circuit | Max distance at 3 percent, 120 V | Drop at 100 ft, 120 V | Max distance at 3 percent, 240 V |
|---|---|---|---|
| 10 A | 93 ft | 3.86 V (3.2 percent) | 186 ft |
| 15 A | 62 ft | 5.79 V (4.8 percent) | 124 ft |
| 20 A | 46 ft | 7.72 V (6.4 percent) | 93 ft |
The 240 V column doubles the 120 V distances for the same loads, because the drop in volts is identical and the percentage is figured against twice the voltage. It is the quiet reason 240 V circuits for wells, workshops and EV charging forgive runs that would fail badly at 120 V. The 100 ft column is the reality check for the runs people actually ask about: a fully loaded 20 A circuit at 100 feet is not marginally over the guideline, it is at more than twice it.
What the 3 percent figure is, and is not
The 3 percent target comes from informational notes in 210.19 and 215.2, which recommend sizing so that drop stays within 3 percent on a branch circuit or feeder and 5 percent on the two combined. Informational notes are guidance, not enforceable code text, and exceeding them is not a violation by itself. What exceeding them does is physical, not legal. A motor at the end of a dropped run starts slower, draws its starting current longer, and runs hotter doing the same work. A heater's output falls with the square of the voltage, so a 6 percent drop costs it about 12 percent of its heat. Lights dim visibly when a large load on the same run switches in. The guideline exists because equipment feels those numbers, and the voltage drop calculator works the percentage for your own load, length and conductor rather than a table's assumptions.
Why the load current dominates
Drop is proportional to current and to length, multiplied together. That single fact reorganises most distance questions. A 12 AWG run to a detached building carrying a 5 A lighting and receptacle load stays inside 3 percent past 180 feet; the same wire at 20 A fails before 50 feet. Judging a run by its length alone, "it is only 80 feet", is therefore meaningless until the current is named, and the honest answer to how far 12 gauge can run is always a load figure wearing a distance figure's clothes. It also explains the field experience that long runs "worked fine for years" and then failed: the wire did not change, the load did, when a space heater, a compressor or a charger joined the circuit and doubled the current the drop is figured on.
When to step up to 10 AWG
Stepping up one size cuts resistance from 1.93 to 1.21 ohms per 1,000 feet, and stretches every distance in the table by the same factor. On 10 AWG copper the 3 percent limits at 120 V become about 148 feet at 10 A, 99 feet at 15 A and 74 feet at 20 A. The step is worth taking when the run is fixed and the load is real: a workshop sub-feed at the end of a long trench route, a well or gate circuit that cannot move closer, a 20 A circuit whose far outlets genuinely serve heavy loads. Two clarifications keep the step honest. The breaker does not change: a 20 A circuit on 10 AWG is still a 20 A circuit, protected at 20 A, with the larger conductor bought for drop rather than ampacity. And where conductors are upsized for drop, the equipment grounding conductor grows in proportion under 250.122(B), a detail long-run work forgets at its peril. The wire size calculator runs ampacity and drop together and names which check governed, which is the fastest way to see whether your run is a 12 AWG job, a 10 AWG job, or a 240 V job.
A worked run: the 90 ft garage
Put the table to work on the run that prompts the question most often: a detached garage 90 feet from the panel, on a 20 A circuit whose realistic heavy load is 15 A, a saw or a heater rather than the breaker's full rating. On 12 AWG the drop at 15 A over 90 feet is 5.21 V, or 4.3 percent: over the branch-circuit guideline, inside the 5 percent combined figure if the feeder ahead of it drops little, and tolerable for lighting and intermittent tools while being genuinely poor for a heater that will sit at full draw. On 10 AWG the same run drops 3.27 V, or 2.7 percent, inside the guideline with the breaker unchanged at 20 A. Split the budget the way designers usually do, holding the feeder to about 2 percent and the branch circuit to about 3, and the 10 AWG answer is the one that leaves the installation nothing to apologise for. The exercise generalises: name the load honestly, measure the run once, and the table picks the wire.
Planning only
This guide is a planning reference built on NEC 2023 methods. The 3 and 5 percent figures are the NEC's informational-note recommendations, not limits your jurisdiction may or may not adopt as rules, and the final conductor selection for a real installation belongs with your authority having jurisdiction and your licensed electrician.