Sub-Panel Wire Size Chart - Feeders from 30 to 200 Amps

A sub-panel feeder is sized at full ampacity, with no dwelling service allowance: this chart pairs feeder breakers from 30 to 200 amps with the copper and aluminum conductors and the ground wire each one takes, then works the distance check that changes the answer on long runs.

Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.

The chart

Each row is the smallest conductor whose Table 310.16 ampacity at 75 C reaches the feeder breaker rating, with the small-conductor caps of 240.4(D) applied, and the equipment grounding conductor from Table 250.122 for the same breaker. Ampacity is the floor, before derating and before voltage drop.

Feeder breakerCopperAluminumGround wire (copper)
30 A10 AWG8 AWG10 AWG
40 A8 AWG8 AWG10 AWG
50 A8 AWG6 AWG10 AWG
60 A6 AWG4 AWG10 AWG
80 A4 AWG2 AWG8 AWG
100 A3 AWG1 AWG8 AWG
125 A1 AWG2/0 AWG6 AWG
150 A1/0 AWG3/0 AWG6 AWG
200 A3/0 AWG250 kcmil6 AWG

Two rows repay a second look. At 30 A the aluminum column starts at 8 AWG, not 10 AWG: 10 AWG aluminum has the ampacity on paper, but 240.4(D) caps the breaker that may protect it well below 30 A. And at 100 A both metals land exactly on the breaker rating, 3 AWG copper at 100 amps and 1 AWG aluminum at 100 amps, which leaves nothing for derating. A feeder run through a hot attic or bundled with other conductors can need the next size up on those rows before voltage drop is even considered. The wire size calculator applies your derating conditions and the drop check to the same run in one pass.

Why a sub-panel feeder is not a service

The most common feeder mistake is borrowing the service answer. NEC 310.12 lets a dwelling service be sized to 83 percent of its rating, which is why a 100 amp service takes 4 AWG copper. That allowance belongs to services and to feeders carrying the entire load of a dwelling unit. A feeder to a sub-panel in a garage, an addition or a workshop carries part of the load, on conductors the code sizes at full ampacity: the same 100 amps takes 3 AWG copper as a feeder, one size larger than the service answer.

The reasoning is load shape. A whole dwelling is diverse: the service never sees every load at once, and decades of measurement sit behind the 83 percent figure. A sub-panel's load is whatever its circuits are doing, and a workshop panel can sit at its feeder rating for hours. If the feeder genuinely carries the entire dwelling load, the allowance can apply; that is a whole-house feeder between the meter and the only panel, not a sub-panel in the usual sense.

Four wires, and an isolated neutral

A modern sub-panel feeder is four conductors: two ungrounded, a neutral, and an equipment grounding conductor. The neutral is not optional on a panel serving 120 volt loads, and it is sized from the feeder's unbalanced load like any neutral. What changes at the sub-panel is the bonding. The neutral is bonded to the service enclosure at the service only. At the sub-panel the neutral bar floats, isolated from the enclosure, and the grounding bar bonds to the box and to the equipment grounding conductor in the feeder. Bonding the neutral again downstream puts neutral current on the grounding path, which is the fault the separation exists to prevent.

The ground wire in the chart is the equipment grounding conductor, sized from the feeder breaker by Table 250.122, not from the conductor size. The grounding conductor size calculator works that table, and the 250.66 electrode table beside it, from your breaker and service sizes. One growth rule rides along: when the ungrounded conductors are upsized for voltage drop, 250.122(B) grows the equipment grounding conductor in the same proportion, so a long feeder can pull its ground wire up a size as well.

Derating can move the row too

The chart assumes the conductors run at reference conditions. Add current-carrying neighbours or heat and the adjustment factors of 310.15 start from the 90 C column and can move a feeder up a row before distance is considered. The 100 A row shows it plainly: 3 AWG copper starts at 115 A in the 90 C column, and with four to six current-carrying conductors in the raceway the 0.80 adjustment leaves 92 A, below the breaker. The next size, 2 AWG, starts at 130 A, adjusts to 104 A, and holds the 100 A feeder. Rows that land exactly on the breaker rating, 100 A in both metals and 50 A in aluminum, are the exposed ones; rows with a step of headroom absorb ordinary derating without moving.

Distance: when the run forces an upsize

Feeders are where voltage drop stops being a footnote, because sub-panels live at the ends of runs: across a house, out to a barn, down a long trench. The chart above is an ampacity answer. The drop check uses the site's Chapter 9 resistance basis at the full feeder load, holding drop to the customary 3 percent target on a 240 volt run.

Take the 100 amp row. At 150 feet one-way, the chart's 3 AWG copper drops 7.35 volts at 100 amps, which is 3.06 percent: just over the target. One size up, 2 AWG, drops 5.82 volts, or 2.43 percent, and governs the job. The effect sharpens on smaller feeders. A 60 amp feeder at 200 feet starts from 6 AWG on ampacity, but 6 AWG drops 4.91 percent at full load, 4 AWG still drops 3.08 percent, and the run lands on 3 AWG, three sizes above the chart row, before it satisfies the drop target. Real feeders rarely sit at full load for long, and drop falls in proportion to load, so these are conservative figures; but a feeder sized to them never explains dim lights at the far end. When the run is long, check the voltage drop at your real load and length, and let the breaker size calculator confirm the device at the supply end.

Detached buildings get an electrode too

A sub-panel in a separate structure needs more than the feeder. Under 250.32, a building supplied by a feeder requires its own grounding electrode system at that building, rods, a concrete-encased electrode or whatever qualifies on the site, connected to the feeder's equipment grounding conductor and the panel's grounding bar. The electrode does not replace the equipment grounding conductor run with the feeder on new work; the two do different jobs, one tying the local system to earth, the other clearing faults back to the source. Older installations exist under older rules, and what may be kept or must be brought forward on a panel change is a question for the local authority, not for a chart.

Planning only

This guide is a planning reference built on NEC 2023 methods. Feeder work is permit work in nearly every jurisdiction, local amendments vary, and the final conductor selection for a real installation belongs with your authority having jurisdiction and your licensed electrician.