What Size Breaker for a Water Heater - 4500 W and 5500 W Worked Out
For the standard 4500 W storage water heater at 240 V, the answer is a 25 A breaker on 10 AWG copper. This guide works that answer out of the continuous-load rule, then takes the 5500 W case, the 208 V case, and the tankless units where the simple answer stops.
Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.
The standard case, worked
A storage water heater is a continuous load in the code's eyes: NEC 422.13 requires its branch circuit to be sized at 125 percent of the heater's rating, because a recovery cycle after a morning of showers can hold the element on for three hours or more. The arithmetic for the commonest unit in North America runs in three steps.
First, the current: 4500 W at 240 V is 18.75 A. Second, the continuous factor: 18.75 times 1.25 is 23.44 A. Third, the standard rating at or above that figure from the 240.6 list: a 25 A breaker. The conductor follows the same 23.44 A floor. Here a quiet rule decides the wire: 12 AWG copper has 25 A of ampacity at 75 C, enough on paper, but 240.4(D) caps the breaker protecting 12 AWG at 20 A, and a 20 A breaker is below the 23.44 A the load requires. So the circuit lands on 10 AWG copper, which carries 35 A at 75 C and pairs with the 25 A breaker cleanly. The breaker size calculator runs this same sequence, continuous factor first, then the next standard rating up, for any load you give it.
Why the 125 percent exists
Breakers and conductors are thermal devices. A breaker carrying current at its full rating for hours runs at the edge of its calibration, and a conductor at full ampacity runs at its insulation's rated temperature with no margin for a hot attic, a tight bundle or an ageing termination. The 125 percent factor buys the margin back: the circuit is built so that a load which can genuinely run all day sits at 80 percent of the circuit's rating instead. Loads that cycle, a cooktop element or a compressor, do not get the factor. A storage water heater recovering a cold tank does, and the code names it directly rather than leaving the judgement to the installer.
The 5500 W case, the 208 V case, and the smaller unit
The same three steps cover the rest of the storage range. A 5500 W element at 240 V draws 22.92 A; times 1.25 is 28.65 A; the next standard rating is a 30 A breaker, and 10 AWG copper, capped at exactly 30 A by 240.4(D) and carrying 35 A at 75 C, is again the wire. Voltage matters as much as wattage: the same 4500 W heater fed at 208 V, common in smaller commercial services, draws 21.63 A, and times 1.25 is 27.04 A, which also lands on a 30 A breaker and 10 AWG. At the small end, a 3800 W unit at 240 V draws 15.83 A, times 1.25 is 19.79 A, and a 20 A breaker on 12 AWG copper is the complete answer.
Two nameplate cautions close the storage cases. Some heaters are marked with a specific maximum breaker or a minimum circuit ampacity, and manufacturer instructions carry the force of the listing under 110.3(B): where the plate speaks, it outranks any chart, including this one. And a dual-element heater almost never runs both elements at once; the non-simultaneous interlock is why the circuit is sized on one element's wattage, not the sum printed across two lines of the label. If a unit is genuinely simultaneous, its nameplate current says so, and that figure is the one to run.
The element swap trap
One repair quietly breaks the arithmetic. Heating elements are replaceable parts, and a 4500 W element and a 5500 W element often share the same thread and fit the same tank. A heater that left the factory at 4500 W on a 25 A circuit can come back from a repair with a 5500 W element drawing 22.92 A, which at the continuous factor needs 28.65 A of circuit: the 25 A breaker is now undersized for the load it protects, and nuisance tripping on long recovery cycles is the polite version of the failure. The circuit belongs to the element actually installed, so an element change is a circuit check, in both directions: the larger element wants the 30 A circuit worked above, and nothing about the smaller circuit may be assumed to carry it.
Tankless: where the simple answer stops
Whole-house tankless units leave the storage pattern behind. Typical residential models are rated in the 18 to 27 kW range; the top of that range at 240 V is 112.5 A before any sizing factor, more than many services carry in total. Manufacturers answer with subdivision: the unit arrives as two or three internal heating circuits, each with its own breaker requirement stated in the instructions, commonly two or three breakers in the 40 A class feeding one appliance. There is no chart answer for that arrangement, and any guide that offers one is guessing. The instruction sheet's circuit table, the service's spare capacity, and a load calculation decide the job, in that order. Point-of-use tankless units at a single sink are the opposite case: small, nameplate-driven, and sized exactly like the storage examples above from their stated wattage. The wire size calculator checks the conductor for whichever circuit the instructions specify, including the voltage drop on a long run to an outbuilding heater.
Planning only
This guide is a planning reference built on NEC 2023 methods. Water heater circuits are permit work in most jurisdictions, the manufacturer's instructions govern the specific unit, and the final selection for a real installation belongs with your authority having jurisdiction and your licensed electrician.