What Size Wire for a 100 Amp Service - With Distance and Voltage Drop Checks

For a 100 amp dwelling service, the answer is 4 AWG copper or 2 AWG aluminum under NEC 310.12. This guide shows where that answer comes from, why a 100 amp sub-panel feeder gets a different one, and what distance does to both.

Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.

The direct answer

NEC 310.12 sizes dwelling service conductors to 83 percent of the service rating, reflecting how diverse a house's loads really are. For a 100 amp service, 83 percent is 83 amps of required ampacity. In Table 310.16 at 75 C, 4 AWG copper carries 85 amps and 2 AWG aluminum carries 90 amps, so those are the minimum sizes: 4 AWG copper or 2 AWG aluminum for a qualifying 100 amp dwelling service.

Without the 310.12 allowance, the straight ampacity answer is one step up: the conductors need a full 100 amps, which is 3 AWG copper (100 amps) or 1 AWG aluminum (100 amps). Which pair applies to your job depends on what the conductors are doing, and that distinction is where most wrong answers come from.

Service vs sub-panel feeder: why the answers differ

The 83 percent allowance belongs to services and to feeders that carry the entire load of a dwelling unit. A 100 amp feeder to a sub-panel, carrying the garage, an addition, or part of the house, is neither. Its conductors are sized at full ampacity under the ordinary rules: 3 AWG copper or 1 AWG aluminum for a 100 amp feeder breaker, before derating and before voltage drop.

This is not a technicality. The allowance exists because a whole dwelling's load is diverse and well measured. A sub-panel's load is whatever is plugged into it, and a workshop sub-panel can sit near its feeder rating for hours. So the same "100 amp wire" question has two correct answers: 4 AWG copper for the service, 3 AWG copper for the sub-panel feeder, and mixing them up undersizes the feeder. The wire size calculator runs the feeder case directly: enter the load, apply your derating conditions, and it checks voltage drop on the same run.

Distance and voltage drop

At 100 amps the table sizes are small conductors with real resistance, so distance bites sooner than it does on a 200 amp service. The table below uses the same Chapter 9 resistance basis as this site's calculators, at the full 100 amp load on a 240 volt service, one-way distance, holding voltage drop to the customary 3 percent target:

One-way distanceCopperAluminum
50 ft4 AWG2 AWG
100 ft4 AWG2 AWG
150 ft2 AWG1/0 AWG
200 ft1 AWG2/0 AWG
300 ft2/0 AWG4/0 AWG

Read the pattern, not just the rows. At 100 feet the ampacity answer still governs. By 150 feet voltage drop has taken over, and by 300 feet the conductor is two to three sizes above the table minimum. Two things soften this in practice: the drop is computed at the full 100 amps, which a real service touches rarely, and drop falls in proportion to load, so at 50 amps every figure in the table roughly halves. What does not soften is a long run to a detached building at a genuinely heavy load. When the run is long, check the voltage drop with your real load and length before the trench is dug, not after the lights dim.

The upgrade question: is 100 amps enough?

Half the people asking about 100 amp wire are really asking whether to keep a 100 amp service or upgrade. Wire size cannot answer that; a load calculation can. A smaller home with gas heat, a gas range and no EV charging often calculates comfortably inside 100 amps. Add electric heat, an electric range and dryer, and a 48 amp EV charger, and the same house can calculate past it.

The trap is judging by breaker count. Panel breakers sum to far more than any service rating because Article 220 demand factors recognise that loads do not peak together. The honest route is the calculation: the service size calculator turns a demand-adjusted total into the standard rating it lands on, and if the total is close to the line, the dwelling load calculation behind it is worth doing load by load.

Ground and neutral notes

The grounding electrode conductor follows Table 250.66 from the service conductor size. A 100 amp service on 4 AWG copper conductors falls in the smallest band of the table, taking an 8 AWG copper grounding electrode conductor. The neutral is sized from the calculated unbalanced load under 220.61 and may not be smaller than that grounding electrode conductor size, per 250.24(C). On most 100 amp dwelling services the neutral ends up the same size as the ungrounded conductors or one size smaller; both outcomes come out of the calculation, not out of habit. The grounding conductor size calculator works both tables from your breaker and conductor sizes.

The panel is not the service

One confusion follows this question around: a 100 amp panel does not prove a 100 amp service, and a 100 amp main breaker does not size the conductors by itself. Older homes carry panels that were replaced without a service upgrade, services that were upgraded without a panel change, and main breakers chosen for the panel's bus rating rather than the service size. The conductor size follows the service rating and the load calculation, and where the paperwork and the equipment disagree, the load calculation is the document that settles what the installation actually is. If you are planning around a panel you already own, read its label for the bus rating and the main breaker size, then treat both as facts about the panel only.

Copper or aluminum at 100 amps

At 200 amps the material choice is mostly economic. At 100 amps a second consideration appears: the conductors are small enough that termination quality dominates. Aluminum at 2 AWG is a perfectly sound service conductor with listed lugs, anti-oxidant where the lug maker requires it, and torque applied to specification. It is also the size range where a careless termination runs hot for years before it announces itself. Copper at 4 AWG is more forgiving of technique and fits anywhere. Neither answer is wrong; the choice is between aluminum installed carefully and copper installed ordinarily, and on a short run the price gap between them is small enough that many electricians default to copper at this size and aluminum at 200 amps. Whichever you choose, the size comes from the table for that material, and the two columns are never mixed on the same run.

One more practical check: mobile home services and feeders carry their own article (Article 550) with its own conductor requirements, and a 100 amp mobile home feeder is a common place for the general answer in this guide to be superseded. If the building is a manufactured home, the specific article and the home's own data plate govern.

Planning only

This guide is a planning reference built on NEC 2023 methods. Service changes are utility-coordinated, permit work in nearly every jurisdiction, and the final conductor selection for a real installation belongs with your authority having jurisdiction and your licensed electrician.