What Size Wire for a 200 Amp Service - Copper, Aluminum and the 83% Rule
For a 200 amp dwelling service, the short answer is 2/0 AWG copper or 4/0 AWG aluminum. This guide explains the NEC 310.12 rule that produces those sizes, when the rule does not apply, and how distance changes the answer.
Built to NEC 2023 tables. No reviewer claim until a licensed reviewer is signed.
The direct answer
A 200 amp residential service, or a feeder that carries the entire load of a dwelling, is sized under NEC 310.12. That section lets the service conductors be sized to 83 percent of the service rating, because a dwelling's loads are diverse: nothing in a house runs everything at full current at once, and decades of load data sit behind the allowance. 200 amps times 0.83 is 166 amps of required ampacity. Read against Table 310.16 at 75 C, the first copper size that covers 166 amps is 2/0 AWG at 175 amps, and the first aluminum size is 4/0 AWG at 180 amps.
So for a qualifying dwelling service: 2/0 AWG copper or 4/0 AWG aluminum. If your run is short and the service equipment is close to the meter, that is usually the whole answer. The rest of this guide covers the cases where it is not: services the 83 percent rule does not reach, and runs long enough that voltage drop takes over from ampacity.
When the 83 percent rule applies, and when it does not
The allowance is narrower than its reputation. It applies to single-phase, 120/240 volt dwelling services and to feeders that carry the entire load associated with a dwelling unit. Three boundaries matter:
- Commercial services never qualify. A 200 amp commercial service is sized straight from Table 310.16 with no reduction: 3/0 AWG copper (200 amps) or 250 kcmil aluminum (205 amps).
- A feeder to a sub-panel usually does not qualify. If the feeder carries only part of the dwelling's load, the allowance is gone and the same straight-table answer applies. Only a feeder carrying the whole dwelling load, such as the run from an exterior main disconnect to the main panel, keeps it.
- The conductors still have to land on rated terminations. The 75 C column is the working basis because service equipment terminations are rated 75 C, which is the column the sizes above come from.
Getting this boundary wrong is the most common error with the rule. If your 200 amp run is a sub-panel feeder or feeds anything commercial, use 3/0 copper or 250 kcmil aluminum and check voltage drop from there.
Copper vs aluminum
Both materials are legal and common at this size, and the choice is practical rather than electrical. Aluminum service conductors are the default on most new homes: the conductor is larger for the same ampacity, but it is lighter and is the usual budget choice where the budget matters. Copper is more compact, which helps in tight service equipment, and its terminations are less technique-sensitive.
Aluminum asks for three habits in return. The terminations must be rated for aluminum (service lugs are, and are marked AL/CU), the conductor ends get anti-oxidant compound where the lug manufacturer requires it, and the lugs get torqued to the printed specification rather than by feel. Most aluminum service failures are termination failures, not conductor failures. Whichever material you choose, the size comes from the same table; only the column changes.
Distance: when voltage drop takes over
Ampacity is a heat check and does not care how long the run is. Voltage drop does. At the full 200 amps on a 240 volt service, the table sizes hold drop to about 3 percent out to roughly 150 feet. Past that, the conductor has to grow, and the growth is steep because a service runs at high current. The table below is computed with the same Chapter 9 resistance basis as this site's calculators, at the full 200 amp load, one-way distance, holding drop to 3 percent:
| One-way distance | Copper | Aluminum |
|---|---|---|
| 50 ft | 2/0 AWG | 4/0 AWG |
| 100 ft | 2/0 AWG | 4/0 AWG |
| 150 ft | 2/0 AWG | 4/0 AWG |
| 200 ft | 3/0 AWG | 250 kcmil |
| 300 ft | 250 kcmil | 400 kcmil |
Two honest qualifications. First, real services almost never sit at a continuous 200 amps, so a drop figure computed at full load is a worst case; at half load the drop halves. Second, 3 percent is a design target from the NEC's informational notes, not an enforceable limit. What is enforceable is that the equipment at the far end works, and motors, electronics and long lighting runs all complain first when drop grows. Run your own distance through the voltage drop calculator and the wire size calculator together: one isolates the drop, the other runs drop and derated ampacity on the same inputs and names the governing size.
Grounding electrode conductor and neutral
The ungrounded conductors get the attention, but two other conductors are sized on every service. The grounding electrode conductor follows Table 250.66, keyed to the service conductor size: a 2/0 copper service takes a 4 AWG copper grounding electrode conductor, and a 4/0 aluminum service takes a 2 AWG copper one. The grounding conductor size calculator covers both that table and the equipment grounding conductor table.
The neutral is different again. It carries only the unbalanced load, so it is sized from the calculated neutral load under 220.61 rather than from the service rating, with a floor: it may not be smaller than the grounding electrode conductor size required by 250.24(C). On a typical 200 amp dwelling service the neutral commonly lands one or two sizes below the ungrounded conductors, but that is an outcome of the calculation, not a rule to copy.
When to upsize beyond the table
There are good reasons to land above the minimum even on a short run. A planned EV charger, a future panel upgrade path, or a heat pump conversion all argue for conductor headroom while the trench or the wall is open. Some utilities impose their own service conductor requirements on the line side of the meter, and those govern where they apply. And where a long run is borderline on voltage drop at full load, the next size up buys back voltage that every motor in the house will feel on starting. Upsizing conductors is always legal; undersizing them never is. If you are deciding whether the service itself should be 200 amps at all, that is a load question: the service size calculator turns an Article 220 total into the rating it supports.
Errors this question hides
Three mistakes account for most wrong 200 amp answers. The first is applying the 83 percent rule where it does not belong: to a commercial service, or to a sub-panel feeder that carries only part of the house. Both take the straight table answer, 3/0 copper or 250 kcmil aluminum, and the difference is a conductor size, not a rounding choice. The second is sizing from the 90 C column. High-temperature insulation ratings are real, but termination ratings govern the ampacity you may use, and service equipment terminations are 75 C devices; the 75 C column is the one the sizes in this guide come from. The third is forgetting the utility. Everything on the line side of the meter, and sometimes the meter socket itself, answers to the utility's own service standards as well as the NEC, and those standards can and do call for larger conductors than the code minimum on long service laterals.
Cable assemblies deserve one note of their own. Service-entrance cable and individual conductors in conduit read from the same Table 310.16 columns, so the sizes in this guide hold either way, but the assembly's own listing and the raceway fill and derating rules still apply to the installation as a whole. Where derating under 310.15 applies, it can move the answer up a size on top of everything above.
Planning only
This guide is a planning reference built on NEC 2023 methods. Service work is utility-coordinated, permit work in nearly every jurisdiction, and the final conductor selection for a real service belongs with your authority having jurisdiction and your licensed electrician.